From 8 L to 5000 L
Intended to protect the butyl bag of a downstream expansion vessel from temperature extremes.
Technical description
Applications:
Heating, solar and chilled water systems.
Functions:
Protection against inadmissible temperature in expansion vessels.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: see Articles
Temperature:
Intermediate vessel DD/DU:
Max. admissible temperature, TS: 110 °C
Min. admissible temperature, TSmin: -10 °C
Intermediate vessel DG:
Max. admissible temperature, TS: 180 °C
Min. admissible temperature, TSmin: -10 °C
Material:
Steel. Color beryllium.
Media:
Non-aggressive and non-toxic system media.
Addition of antifreeze agent up to 50%.
Transportation and storage:
In frostless, dry places.
Standard:
Constructed according to PED 2014/68/EU.
The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by IMI Hydronic Engineering without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.imi-hydronic.com.