Acest site web intenționează să utilizeze cookie-uri pentru a îmbunătăți site-ul și pentru a vă oferi o experiență mai bună de navigare. Dacă selectați "Continuați" sau continuați să navigați pe site fără a personaliza opțiunile dvs., sunteți de acord cu utilizarea cookie-urilor noastre. Aflați mai multe despre politica privind cookie-urile și despre modul de refuzare a cookie-urilor făcând clic aici.

Multilux 4-F-Set

For connection radiators with a bottom connection and floor heating is used to control the room temperature and for limitation of the return temperature. Centre-to centre distance of connection is 50 mm. Installation in angle type. Both thermostatic inserts include the V-exact II precision presetting with 8 stepless presetting values.

Informații produs

For radiator two point bottom connection R1/2 or G3/4 with an additional connection for floor heating

For connection radiators with a bottom connection and floor heating is used to control the room temperature and for limitation of the return temperature. Centre-to centre distance of connection is 50 mm. Installation in angle type. Both thermostatic inserts include the V-exact II precision presetting with 8 stepless presetting values.

Key features

Combination of thermostatic valve and return temperature limiter

for bath or designer radiators and additional underfloor heating

Shut-off barriers to radiators and underfloor heating

for maintenance without interrupting operation

Elegant covers

white RAL 9016

V-exact II presetting for hydronic balancing

for radiators and floor heating circuit

Technical description

Applications area:

Two-pipe heating systems
Floor heating systems

Functions:

Individual room temperature control.
Maximum limitation of the floor heating return temperature.
Presetting (V-exact II) at thermostatic valve and return temperature limiter.
Shut-off.

Dimensions:

DN 15

Pressure class:

PN 10

Setting range:

Thermostatic head DX:
6 °C to 28 °C
Return temperature limiter RTL:
0 °C to 50 °C

Temperature:

Max. working temperature: 90°C
Min. working temperature: 2°C
For all Multibox models, ensure that the system supply temperature is suitable for setting up the floor heating system.
See also Information!

Materials:

Valve body: Corrosion resistant Gunmetal.
O-rings: EPDM rubber
Valve disc: EPDM rubber
Return spring: Stainless steel
Valve insert: Brass, PPS (polyphenylsulphide)
The complete thermostatic insert can be replaced using the fitting tool without draining the system.
Spindle: Niro-steel spindle with double O-ring sealing. The outer O-ring can be replaced under pressure.
Cover: ABS

Surface treatment:

Valve body gunmetal, fittings are nickel-plated.

Marking:

THE, RTL and II+ Designation. Flow direction arrows. White protection caps.
H = Supply heating system
HR = Return heating system
F = Supply floor heating
FR = Return floor heating

Radiator connection:

Adapters for R1/2 and G3/4, for radiator connections. Tolerance compensation ±1,0 mm with special union nuts and flexible flat seal system for installation free of tension.

Pipe connection:

G3/4 male thread for compression fittings for plastic, copper, precision steel or multi-layer pipe.

Connection to thermostatic head and RTL head:

M30x1.5, RTL with additional adaptor