Bi-directional thermostatic radiator valve, head and lockshield
The HEIMEIER TRV pack, consists of a Calypso TRV body, D-U or Halo head and lockshield. Designed for application in a two-pipe pumped heating system. The Bi-directional thermostatic radiator valve can be fitted either vertically or horizontally in the flow or return and either end of a radiator giving the installer total flexibility.
Caratteristiche principali
Bi-directional thermostatic radiator valve
can be fitted either vertically or horizontally in the flow or return of a radiator
Angle or axial connection with one kit and straight versions
for various installation options
Termostato a riempimento di liquido con elevata forza di attuazione e regolazione di precisione
Caratteristiche tecniche
Applicazioni:
Impianti di riscaldamento.
Funzioni:
Regolazione
Intercettazione
Dimensioni:
DN 15
Classe di pressione:
PN 10
Temperatura:
Temperatura massima di esercizio: 120°C, con cappuccio o attuatore 100°C.
Temperatura minima di esercizio: -10°C
Materiali:
Corpo valvola: ottone
O-ring: gomma EPDM
Disco valvola: gomma EPDM
Molla di ritorno: acciaio inox
Inserto valvola: ottone
Possibilità di sostituzione dell’inserto termostatizzabile con l’impianto in funzione, mediante il dispositivo di montaggio HEIMEIER.
Asta: Asta in acciaio Niro con doppio O-ring di tenuta. L'O-ring esterno può essere sostituito sotto pressione.
Material thermostatic head:
ABS, PA6.6GF30, brass, steel,
Liquid-filled thermostat.
Trattamento superficiale:
Il corpo valvola e i raccordi sono nichelati.
Marking:
IMI, country code, flow direction arrow, KEYMARK-Designation. II+ Designation.
Black protection cap.
Norme di riferimento:
Le valvole sono conformi ai seguenti requisiti:
– Certificate e testate da KEYMARK secondo DIN EN 215
Pipe connection:
G1/2 male thread with 15 mm compression fitting for copper or precision steel pipe.
Raccordo per testa termostatica e attuatore:
IMI Heimeier M30x1.5
Thermostatic heads:
Closed graduation cap and liquid-filled thermostat. High actuating force, minimum hysteresis, optimum closing time. Stable control response even with minor calculated p-band variations (<1 K). Frost protection.
Thermostatic head D-U: Setting numbers 0–IIIII. Temperature range 0 °C to 28 °C.
Thermostatic head Halo: Setting numbers I–IIIII. Temperature range 6 °C to 28 °C.
I prodotti, i testi, le foto, i grafici nonché i diagrammi presenti in questa brochure possono essere oggetto di variazione da parte di IMI Hydronic Engineering senza alcun preavviso. Per accedere alle informazioni più aggiornate sui nostri prodotti e loro caratteristiche si prega di visitare il sito www.imi-hydronic.it.