Digitally configurable proportional push actuator with electronic fail-safe function – 160/200 N
Digitally configurable fail-safe actuators with or without change-over, and a wide range of setup options provide extensive flexibility for on-site parameter adaptation. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.
Key features
Fully configurable fail-safe
Setting of stroke position (extended, retracted or intermediate position) and delay feature for entering/leaving fail-safe mode for a reliable and optimal fail-safe function.
Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.
Fully configurable
More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.
Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly and health check of fail-safe function.
Quick copying of settings
Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.
Technical description
Functions:
Electronic fail-safe function
Proportional control
Manual override (TA-Dongle)
Stroke detection
Self-adjusting force
Mode, status and position indication
Stroke limitation setting
Minimum stroke setting
Valve blockage protection
Valve clogging detection
Error safe position
Diagnostic/Logging
Delayed start-up
I/O version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ Output signal
R24 version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 1 relay, max. 1A, 30 VAC/VDC on resistive load
+ Output signal
Fail-safe function:
Programmable actuator’s stem extended, retracted or intermediate position on power failure.
Supply voltage:
24 VAC/VDC ±15%.
Frequency 50/60 Hz ±3 Hz.
Power consumption:
Peak: < 6.6 VA (VAC); < 3.2 W (VDC)
Operation: < 2.0 VA (VAC); < 0.9 W (VDC)
Standby: < 1.4 VA (VAC); < 0.45 W (VDC)
Peak consumption occurs for a short period after a power cut for recharging capacitors.
Input signal:
0(2)-10 VDC, Ri 47 kΩ.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
0.33 Hz low pass filter.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC.
Proportional split-range:
0-5, 5-0, 5-10 or 10-5 VDC.
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC.
2-6, 6-2, 6-10 or 10-6 VDC.
Proportional dual-range (for change-over):
0-3.3 / 6.7-10 VDC,
2-4.7 / 7.3-10 VDC,
0-4.5 / 5.5-10 VDC or
2-5.5 / 6.5-10 VDC.
Default setting: Proportional 0-10 VDC.
Output signal:
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Ranges: See “Input signal”.
Default setting: Proportional 0-10 VDC.
Characteristics:
Linear, EQM 0.25 and inverted EQM 0.25.
Default setting: Linear.
Control speed:
10 s/mm
Fail-safe delay:
Adjustable between 0 and 10 seconds.
Default setting: 2 s
Power supply stabilisation delay:
Adjustable between 1 and 5 seconds.
Default setting: 2 s
Pre-charging time:
< 20 s
Adjusting force:
160/200 N
Self-adjusting for IMI Hydronic Engineering valves.
Temperature:
Media temperature: max. 120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +50°C (5-95%RH, non-condensing)
Ingress protection:
IP54
all directions
(according to EN 60529)
Protection class:
(according to EN 61140)
III (SELV)
Cable:
1, 2 or 5 m.
Halogen free with wire end sleeves.
Fire class B2ca – s1a, d1, a1 according to EN 50575.
Type LiYY, 5x0.25 mm2.
Relay cable (R24 version):
1, 2 or 5 m.
Halogen free with wire end sleeves.
Fire class B2ca – s1a, d1, a1 according to EN 50575.
Type LiYY, 3x0.34 mm2.
Stroke:
6,9 mm
Automatic detection of the valve lift (stroke detection).
Noise level:
Max. 30 dBA
Weight:
I/O:
0,20 kg, 1 m.
0,25 kg, 2 m.
0,38 kg, 5 m.
R24:
0,28 kg, 1 m.
0,38 kg, 2 m.
0,67 kg, 5 m.
Connection to valve:
Swivelling nut M30x1,5.
Material:
Cover: PC/ABS GF8
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.
Colour:
White RAL 9016, grey RAL 7047.
Marking:
Label: IMI TA, CE, product name, article No. and technical specification.
Certification CE:
LV-D. 2014/35/EU: EN 60730-1, -2-14.
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 50581.
Product standard:
EN 60730.
The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by IMI Hydronic Engineering without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.imi-hydronic.com.