Thermostatic circulation valve
This thermostatic valve for automatic balancing in domestic hot water systems features a step-less temperature setting, saving energy with reduced delay time for hot water. The shut-off function enables straightforward maintenance while the temperature control feature delivers safer operating procedures. The TA-Therm ZERO is a lead-free product (<0.1% lead content) especially designed to address local environmental demands.
Key features
ZERO lead
Product made of lead-free brass (<0.1% lead content).
Thermometer
For easy maintenance.
Measuring point
For easy maintenance and temperature measuring.
Technical description
Application:
Domestic hot water systems.
Functions:
Stepless temperature setting
Shut-off
Temperature control
Measuring
Dimensions:
DN 15-20
Pressure class:
PN 16
Static pressure:
Max. static pressure during temperature control 10 bar.
Temperature:
Max. working temperature: 90°C
Temperature range:
35-80°C
Pre-set at 55°C
Kv at pre-set temperature: 0,3
Material:
Valve body: Brass CC768S
Valve plug: Corrosion-resistant acetal plastic
Seat: Corrosion-resistant polysulphone plastic
Other parts in contact with water: Brass CW724R (CuZn21Si3P)
O-rings: EPDM rubber
Handwheel: Glassfibre reinforced polyamide plastic
Measuring point: Brass CW724R (CuZn21Si3P)
Sealing: EPDM
Cap: Polyamide and TPE
Marking:
Valve body: TA, ZERO, PN 16, DN, DR, flow direction arrow.
Handwheel: IMI TA
Approvals:
Approved for tap water systems by RISE (Research Institutes of Sweden).