Este sitio web utiliza cookies para mejorar el sitio y proporcionarle una mejor experiencia de navegación. Si selecciona "continuar" o continúa navegando por el sitio sin personalizar sus opciones, acepta nuestro uso de cookies. Obtenga más información sobre nuestra política de cookies y sobre cómo rechazarlas haciendo clic aquí

EMOtec, First-Open

The EMOtec thermal actuator, First-Open with position indicator (NC), can be installed in temperature and/or time related 2-point control systems. The first-open function keeps the actuator open until the individual room control is commissioned.

Información de Producto

Thermal actuator for heating, ventilation, and air conditioning systems

The EMOtec thermal actuator, First-Open with position indicator (NC), can be installed in temperature and/or time related 2-point control systems. The first-open function keeps the actuator open until the individual room control is commissioned.

Key features

Normally closed version with First-Open function

Compact sizes especially suited to manifold cabinets

Simple functional testing by means of position indicator

Trouble-free because it is silent and needs no maintenance

Technical description

Applications:

Designed for ON/OFF or PWM control.

Supply voltage:

24 VAC/VDC (+20%/-10%), 0-60 Hz.
230 VAC (+10%/-10%), 50-60 Hz.

Power consumption:

24 V:
Starting: ≤ 6 W (VA)
During operation: ≤ 2 W (VA)
230 V:
Starting: ≤ 70 W (VA)
During operation: ≤ 2 W (VA)

Operating cycle time:

~ 3 min

Adjusting force:

100 N ±5%

Temperature:

Max. ambient temperature: 60°C
Min. ambient temperature: 0°C
Max. medium temperature: 100°C
Storage temperature: -25°C to +60°C

Enclosure class:

IP54 at any position.

Protection class:

24 V: III, EN 60730
230 V: II, EN 60730

Overvoltage protection:

Version 230 V according to EN 60730-1: 2,5 kV.

Certification:

CE, EN 60730

Cable:

Cable length: 1 m.
Connection cable: 2 x 0,50 mm2.

Stroke:

4 mm

Connection to valve:

M30x1,5

Body:

Polyamide, grey