Differential pressure overflow valve with direct setting value display
Hydrolux is a proportional working, p-band controlled overflow valve with low proportional deviation.
Key features
Direct setting scale display
Low proportional deviation
Extremely low noise, current efficient construction
Low friction valve disc center guide
Highest reaction precision due to an inner setting value spring with generous dimensions
Technical description
Applications:
Heating and cooling systems.
Function:
Proportional relief
Adjustable differential pressure (Δp)
Dimensions:
DN 20-32
Pressure class:
PN 16
Setting range:
50–500 mbar (5-50 kPa).
Adjusted on the operating side and preset to 200 mbar (20 kPa).
300-1800 mbar (30-180kPa).
Adjusted on the operating side and preset to 300 mbar (30 kPa).
Recommended max. volume flow (V):
DN 20: 2,0 m3/h
DN 25: 3,5 m3/h
DN 32: 7,0 m3/h
Max. heat flow (Q):
at Δt 20 K / 10 K
DN 20: 46,5 / 23,3 kW
DN 25: 81,4 / 40,7 kW
DN 32: 162,8 / 81,4 kW
Temperature:
Max. working temperature: 120°C
Min. working temperature: -10°C
Materials:
Body: Corrosion-resistant gunmetal
O-rings: EPDM
Valve disc: EPDM
Spring: Stainless steel
Valve insert: Brass
Spindle: Brass
Handwheel: PA6.6 GF30
Pipe connection:
Female thread connections on the incoming side, female thread or flat sealing lockshield on the out going side.
Threads according to ISO 7/1 (DIN 2999).
Marking:
Body: THE, PN, DN and flow direction arrow.
Handwheel: Heimeier, DN