Ši interneto svetainė ketinai naudoti slapukus, kad pagerintų tinklalapį ir suteiktų geresnę naršymo patirtį. Jei pasirinksite „Tęsti“ arba toliau naršysite svetainėje, nusprendę nepritaikyti nustatymų, bus laikoma, kad sutinkate naudoti slapukus. Sužinokite daugiau apie mūsų slapukų politiką ir kaip atsisakyti slapukų, paspaudę čia.

TA-Slider 160 BACnet/Modbus

Digitally configurable actuators for Bus communication with BACnet MS/TP or Modbus RTU, with or without change-over. A wide range of setup options provide extensive flexibility for on-site parameter adaptation. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.

Produkto informacija

Digitally configurable proportional push actuator for Bus communication with BACnet MS/TP or Modbus RTU – 160/200 N

Digitally configurable actuators for Bus communication with BACnet MS/TP or Modbus RTU, with or without change-over. A wide range of setup options provide extensive flexibility for on-site parameter adaptation. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.

Key features

Convenient, reliable setup

Fully customisable by smartphone via Bluetooth using a TA-Dongle.

Fully configurable

More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.

Easy diagnostics

Tracks the last 10 errors to allow system faults to be found quickly.

Quick copying of settings

Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.

Technical description

Functions:

Proportional control
Manual override
Stroke detection
Mode, status and position indication
Stroke limitation setting
Valve blockage protection
Valve clogging detection
Error safe position
Diagnostic/Logging

BACnet/Modbus version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 1 connection for Pt1000 temperature probe.

BACnet/Modbus CO (change-over) version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 2 connections for Pt1000 temperature probe.
+ 1 relay, internally wired for control of TA-M106 actuator on TA-6-way valve (max. 2A, 30 VAC/VDC on resistive load).

Supply voltage:

24 VAC/VDC ±15%.
Frequency 50/60 Hz ±3 Hz.
BACnet/Modbus CO:
24 VAC only for enabling powering of TA-M106 actuator.

Power consumption:

BACnet/Modbus:
Operation: < 1.5 VA (VAC); < 1.0 W (VDC)
Standby: < 1.2 VA (VAC); < 0.75 W (VDC)
BACnet/Modbus CO:
Operation: < 1.5 VA (VAC)
Standby: < 1.2 VA (VAC)
TA-M106 actuator consumption must be added separately.

Input signal:

By BACnet/Modbus or with hybrid control mode;
0(2)-10 VDC, Ri 47 kΩ.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
0.33 Hz low pass filter.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC.
Proportional split-range:
0-5, 5-0, 5-10 or 10-5 VDC.
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC.
2-6, 6-2, 6-10 or 10-6 VDC.
Proportional dual-range (for change-over):
0-3.3 / 6.7-10 VDC or
2-4.7 / 7.3-10 VDC.
Default setting: By BACnet/Modbus. If Hybrid mode chosen, default input signal is Proportional 0-10 VDC.

Output signal:

By BACnet/Modbus.

Characteristics:

Linear, EQM 0.25 and inverted EQM 0.25.
Default setting: Linear.

Control speed:

10 s/mm

Adjusting force:

160/200 N

Self-adjusting for IMI Hydronic Engineering valves.

Temperature:

Media temperature: max. 120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)

Ingress protection:

IP54

(all directions)

(according to EN 60529)

Protection class:

(according to EN 61140)

III (SELV)

Cables:

Separate overmoulded cables (see Additional equipment).
Type LiYCY 5x0.34 mm2 (cables A and B) and type LiYY 6x0.34 mm2 (cable C).
Relay cable (CO version):
Type LiYY 3x0.34 mm2.
1, 2 or 5 m. With connector to actuator TA-M106.

Stroke:

6,9 mm

Automatic detection of the valve lift (stroke detection).

Noise level:

Max. 30 dBA

Weight:

BACnet/Modbus: 0.22 kg
BACnet/Modbus CO:
0.26 kg, 1 m relay cable.
0.31 kg, 2 m relay cable.
0.45 kg, 5 m relay cable.

Connection to valve:

Swivelling nut M30x1,5.

Material:

Cover: PC/ABS GF8
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.

Colour:

White RAL 9016, grey RAL 7047.

Marking:

Label: IMI TA, CE, product name, article No. and technical specification.

Certification CE:

LV-D. 2014/35/EU: EN 60730-1, -2-14.
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 50581.

Product standard:

EN 60730.

The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by IMI Hydronic Engineering without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.imi-hydronic.com.

Produktai

Animacija

Pasinaudodami šia interaktyvia animacija galite sumodeliuoti, kaip realiose ŠVOK sistemose veikia mūsų pažangūs produktai. Paspauskite paleidimo mygtuką ir pradėkite!

Text for Tenders